CJX2-4011 Contactor

Model Number CJX2-0911 CJX2-1211 CJX2-1811 CJX2-2511 CJX2-3211 CJX2-4011 CJX2-5011 CJX2-6511 CJX2-8011 CJX2-9511
Main circuit characteristics
Pole number 3Pole
Rated insulation voltage (Ui) V 690
Conventional thermal current (th)
AC-1 rated working current
20 20 32 40 50 50 60 80 125 125
Rated working
current (Ie)
AC-3,380/400V A 9 12 18 25 32 40 50 65 80 95
AC-3,660/690V A 6.6 8.9 12 18 22 34 39 42 49 49
AC-4,380/400V A 3.5 5 7.7 8.5 12 18.5 24 28 37 44
AC-4,660/690V A 1.5 2 3.8 4.4 7.5 9 12 14 17.3 21.3
AC-3,220/240V KW 2.2 3 4 5.5 7.5 11 15 18.5 22 25
Rated working
power(Pe)
AC-3,380/400V KW 4 5.5 7.5 11 15 18.5 22 30 37 45
AC-3,415/440V KW 4 5.5 9 11 15 22 25/30 37 45 45
AC-3,500V KW 5.5 7.5 10 15 18.5 22 30 37 55 55
AC-3,660/690V KW 5.5 7.5 10 15 18.5 30 33 37 45 45
AC-4,380/400V KW 1.5 2.2 3.3 4 5.4 7.5 11 15 18.5 22
AC-4,660/690V KW 1.1 1.5 3 3.7 5.5 7.5 10 11 15 18.5
Mechanical lif 10000
times
1200 1000 900 650
Electrical life AC-3 10000
times
110 90 65
AC-4 10000
times
22 22 17 11
Operating
frequency
AC-3 Times/
hour
1200 600
AC-4 Times/
hour
300 300
Without terminal blocks 2 wire mm² 1...4 1.5... 2.5...10 4...25
Tightening torque N-m 1.2 1.8 5 9
Coil
50/60Hz V 24、36、48、110、127、220/230、240、380/400、415、440
Allow control
circuit voltage(Us)
Working V The installation tilt angle is  ±22.5° :85%~110%Us;   The installation tilt angle is±5°:   70%~120%
Release V The installation tilt angle is ±22.5° ,20%~75%US;The installation tilt angle is±5°:  20%~65%
Coil power
consumption
Actuation VA 60 70 200 200
Maintain VA 6-9.5 6-9.5 15-20 15-20
Consumption W 1-3 1-3 6-10 6-10
Auxiliary contact
Contact specifications A 11
Conventional thermal
current(th)
A 10
Rated operational
voltage(Ue)
AC V 380
DC V 220
Rated control capacity AC-15 VA 360
DC-13 W 33
CERTIFICATE CE